EHSHB04P30BA / ERLQ004CAV3 EHSHB08P50BA / ERLQ006CAV3 EHSHB08P30BA / ERLQ006CAV3 EHSHB08P30BA / ERLQ008CAV3 EHSHB08P50BA / ERLQ008CAV3 EHSHB16P50BA / ERLQ011CAV3 EHSHB16P50BA / ERLQ014CAV3 EHSHB16P50BA / ERLQ016CAV3
Innengerät EHSHB04P30BA EHSHB08P50BA EHSHB08P30BA EHSHB08P30BA EHSHB08P50BA EHSHB16P50BA EHSHB16P50BA EHSHB16P50BA
Außengerät ERLQ004CAV3 ERLQ006CAV3 ERLQ006CAV3 ERLQ008CAV3 ERLQ008CAV3 ERLQ011CAV3 ERLQ014CAV3 ERLQ016CAV3
Heizleistung Min. kW 1.80 (1), 1.81 (2) 1.80 (1), 1.81 (2) 1.80 (1), 1.81 (2) 1.80 (1), 1.81 (2) 1.80 (1), 1.81 (2)      
  Nom. kW 4.26 (3), 3.47 (4), 4.53 (1), 3.98 (2) 5.14 (3), 4.60 (4), 6.06 (1), 5.78 (2) 5.14 (3), 4.60 (4), 6.06 (1), 5.78 (2) 5.53 (3), 5.51 (4), 7.78 (1), 7.27 (2) 5.53 (3), 5.51 (4), 7.78 (1), 7.27 (2) 5.95 (3), 7.74 (4), 11.8 (1), 10.4 (2) 14.8 (5), 13.7 (6), 8.28 (3), 9.57 (4) 15.3 (5), 14.9 (6), 8.04 (3), 10.1 (4)
  Max. kW 4.90 (1), 5.12 (2) 8.35 (1), 7.95 (2) 8.35 (1), 7.95 (2) 10.0 (1), 9.53 (2) 10.0 (1), 9.53 (2) 11.4 (1), 11.0 (2) 14.6 (1), 13.6 (2) 16.1 (1), 15.2 (2)
Leistungsaufnahme Heizen Nom. kW 0.870 (5), 1.04 (6), 1.49 (3), 0.850 (4) 1.30 (5), 1.58 (6), 1.88 (3), 1.26 (4) 1.30 (5), 1.58 (6), 1.88 (3), 1.26 (4) 1.69 (5), 2.04 (6), 1.98 (3), 1.56 (4) 1.69 (5), 2.04 (6), 1.98 (3), 1.56 (4) 2.57 (5), 3.13 (6), 2.43 (3), 2.35 (4) 3.42 (5), 4.07 (6), 3.17 (3), 2.93 (4) 3.42 (5), 4.07 (6), 3.17 (3), 2.93 (4)
    Max. kW 1.12 (5), 1.44 (6) 1.99 (5), 2.32 (6) 1.99 (5), 2.32 (6) 2.54 (5), 2.96 (6) 2.54 (5), 2.96 (6) 2.64 (5), 3.25 (6) 3.43 (5), 4.22 (6) 3.83 (5), 4.71 (6)
COP 5.23 (5), 3.84 (6), 2.85 (3), 4.07 (4) 4.65 (5), 3.66 (6), 2.73 (3), 3.64 (4) 4.65 (5), 3.66 (6), 2.73 (3), 3.64 (4) 4.60 (5), 3.57 (6), 2.78 (3), 3.54 (4) 4.60 (5), 3.57 (6), 2.78 (3), 3.54 (4) 4.38 (5), 3.32 (6), 2.45 (3), 3.29 (4) 4.27 (5), 3.34 (6), 2.58 (3), 3.22 (4) 4.10 (5), 3.22 (6), 2.44 (3), 3.15 (4)
Pump Type   Grundfos UPM3 25-75 CHBL Grundfos UPM3 25-75 CHBL Grundfos UPM3 25-75 CHBL Grundfos UPM3 25-75 CHBL Grundfos UPM3 25-75 CHBL Grundfos UPM3 25-75 CHBL Grundfos UPM3 25-75 CHBL Grundfos UPM3 25-75 CHBL
  Gerät mit nominalem externen statischen Druck Heizen kPa 46.0 (9), 48.0 (10) 40.0 (9), 41.0 (10) 40.0 (9), 41.0 (10) 37.0 (9), 36.0 (10) 37.0 (9), 36.0 (10)      
Wasserseitiger Wärmetauscher Wasserdurchfluss Heizen Nom. l/min 13.0 (9), 11.3 (10) 17.4 (9), 16.6 (10) 17.4 (9), 16.6 (10) 22.3 (9), 20.8 (10) 22.3 (9), 20.8 (10) 33.8 (9), 29.8 (10) 42.4 (9), 39.4 (10) 44.0 (9), 42.6 (10)
General Produktbeschreibung Luft-zu-Wasser-Wärmepumpe   Ja Ja Ja Ja Ja Ja Ja Ja
    Sole-zu-Wasser-Wärmepumpe   Nein Nein Nein Nein Nein Nein Nein Nein
    Wärmepumpenkombination Heizer   Ja Ja Ja Ja Ja Ja Ja Ja
    Niedertemperatur-Wärmepumpe   Nein Nein Nein Nein Nein Nein Nein Nein
    Integrierter Zusatzheizer   Nein Nein Nein Nein Nein Nein Nein Nein
    Wasser-zu-Wasser-Wärmepumpe   Nein Nein Nein Nein Nein Nein Nein Nein
  LW(A) Schallleistungspegel (entsprechend EN14825) Innen dB(A) 39.0 39.0 39.0 39.0 39.0 39.0 39.0 39.0
LW(A) Schallleistungspegel (gemäß EN14825) Außen dB(A) 61.0 61.0 61.0 62.0 62.0 64.0 64.0 66.0
Schallbedingungen Ökodesign-Richtlinie und Energieeffizienzklasse Schallleistung im Heizbetrieb, gemessen gemäß EN12102 unter den Bedingungen von EN14825 Schallleistung im Heizbetrieb, gemessen gemäß EN12102 unter den Bedingungen von EN14825 Schallleistung im Heizbetrieb, gemessen gemäß EN12102 unter den Bedingungen von EN14825 Schallleistung im Heizbetrieb, gemessen gemäß EN12102 unter den Bedingungen von EN14825 Schallleistung im Heizbetrieb, gemessen gemäß EN12102 unter den Bedingungen von EN14825 Schallleistung im Heizbetrieb, gemessen gemäß EN12102 unter den Bedingungen von EN14825 Schallleistung im Heizbetrieb, gemessen gemäß EN12102 unter den Bedingungen von EN14825 Schallleistung im Heizbetrieb, gemessen gemäß EN12102 unter den Bedingungen von EN14825
Raumheizen allgemein Luft-zu-Wasser-Gerät Nenn-Luftstrom (außen) m³/h 2,700 2,820 2,820 2,820 2,820      
  Sonstiges Leistungsregelung   Inverter Inverter Inverter Inverter Inverter Inverter Inverter Inverter
    Cdh (Verschlechterung Heizung)   0.900 0.900 0.900 0.900 0.900 0.900 0.900 0.900
    Pck (Kurbelwannenheizbetrieb) kW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
    Poff (Modus AUS) kW 0.011 0.012 0.012 0.012 0.012 0.050 0.050 0.050
    Psb (Standby-Modus) kW 0.011 0.012 0.012 0.012 0.012 0.050 0.050 0.050
    Pto (Thermostat AUS) kW 0.043 0.048 0.048 0.048 0.048 0.105 0.105 0.105
  Integrierter Zusatzheizer Psup kW 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00
    Art der Energieaufnahme   Elektrisch Elektrisch Elektrisch Elektrisch Elektrisch Elektrisch Elektrisch Elektrisch
Warmwasserbereitung Allgemein Deklariertes Lastprofil   L XL L L XL XL XL XL
    Funktion für feste Wasseraufheizung während Spitzenstunden   Ja Ja Ja Ja Ja Ja Ja Ja
  Durchschnittliches Klima AEC (Jährlicher Stromverbrauch) kWh 1,060 1,650 1,150 1,260 1,800 2,160 2,160 2,160
    Ƞwh (Wasserheizeffizienz) % 103 108 98.0 90.0 99.0 84.0 84.0 84.0
    Qelec (Täglicher Stromverbrauch) kWh 4.75 7.45 5.14 5.63 8.11 9.68 9.68 9.68
    Energieeffizienzklasse Wasserheizung   A A A A A A A A
  Kaltes Klima AEC (Jährlicher Stromverbrauch) kWh 1,220 1,860 1,260 1,390 2,200 2,390 2,390 2,390
    Ƞwh (Wasserheizeffizienz) % 92.0 95.0 89.0 80.0 80.0 76.0 76.0 76.0
    Qelec (Täglicher Stromverbrauch) kWh 5.47 8.38 5.65 6.23 10.0 10.8 10.8 10.8
  Warmes Klima AEC (Jährlicher Stromverbrauch) kWh 948 1,510 1,070 1,140 1,700 1,920 1,920 1,920
    Ƞwh (Wasserheizeffizienz) % 120 117 107 100 106 95.0 95.0 95.0
    Qelec (Täglicher Stromverbrauch) kWh 4.23 6.80 4.76 5.09 8.00 8.60 8.60 8.60
Raumheizen Wasserauslass 55 °C für durchschnittliches Klima Allgemein Jährlicher Energieverbrauch kWh 2,930 3,830 3,830 4,730 4,730 6,350 7,650 8,980
      Saisonale Effizienz Raumheizen % 130 125 125 127 127 125 126 125
      Prated bei -10 °C kW 5.00 6.00 6.00 8.00 8.00 10.0 12.0 14.0
      Saisonale Effizienzklasse Raumheizen   A++ A++ A++ A++ A++ A++ A++ A++
    Bedingung A (-7 °C TK/-8 °C FK) Cdh (Verschlechterung Heizung)   1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
      COPd   2.03 2.09 2.09 2.10 2.10 1.94 1.92 1.85
      Pdh kW 4.20 5.30 5.30 5.40 5.40 9.00 10.9 12.6
      PERd % 81.2 83.6 83.6 84.0 84.0 77.6 76.8 74.0
    Bedingung B (2 °C TK/1 °C FK) Cdh (Verschlechterung Heizung)   1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
      COPd   3.31 3.13 3.13 3.25 3.25 3.30 3.30 3.19
      Pdh kW 2.60 3.10 3.10 3.90 3.90 5.40 6.60 7.80
      PERd % 132 125 125 130 130 132 132 128
    Bedingung C (7 °C TK/6 °C FK) Cdh (Verschlechterung Heizung)   1.00 1.00 1.00 1.00 1.00 0.900 1.00 1.00
      COPd   4.43 4.09 4.09 4.42 4.42 4.26 4.34 4.47
      Pdh kW 1.80 2.10 2.10 2.60 2.60 4.60 4.60 4.90
      PERd % 177 164 164 177 177 170 174 179
    Bedingung D (12 °C TK/11 °C FK) Cdh (Verschlechterung Heizung)   0.900 0.900 0.900 0.900 0.900 0.900 0.900 0.900
      COPd   6.55 5.99 5.99 5.99 5.99 6.30 6.45 6.52
      Pdh kW 2.20 2.00 2.00 2.00 2.00 5.50 5.50 5.40
      PERd % 262 240 240 240 240 252 258 261
    Tol (Temperatur-Betriebsgrenze) COPd   1.64 1.79 1.79 1.79 1.79 1.78 1.63 1.57
      Pdh kW 4.10 5.10 5.10 5.10 5.10 9.10 9.80 11.2
      PERd % 65.6 71.6 71.6 71.6 71.6 71.2 65.2 62.8
      TOL °C -10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0
      WTOL °C 55.0 55.0 55.0 55.0 55.0 55.0 55.0 55.0
    Nenn-Heizleistung Zusatzheizung Psup (bei Tdesign -10 °C) kW 0.700 0.900 0.900 2.40 2.40 1.00 2.50 3.00
    Tbiv (bivalente Temperatur) COPd   2.03 2.09 2.09 2.36 2.36 1.94 1.92 1.84
      Pdh kW 4.20 5.30 5.30 5.80 5.80 9.00 10.9 12.6
      PERd % 81.2 83.6 83.6 94.4 94.4 77.6 76.8 73.6
      Tbiv °C -7.00 -7.00 -7.00 -4.00 -4.00 -7.00 -7.00 -7.00
  Wasserauslass kaltes Klima 55 °C Allgemein Jährlicher Energieverbrauch kWh 3,070 4,010 4,010 4,580 4,580 8,190 9,680 10,400
      Saisonale Effizienz Raumheizen % 109 103 103 109 109 101 100 100
      Prated bei -22°C kW 4.00 4.00 4.00 5.00 5.00 9.00 10.0 11.0
    Bedingung A (-7 °C TK/-8 °C FK) Cdh (Absinken Heizen)   1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
      COPd   2.30 2.47 2.47 2.41 2.41 1.98 2.04 2.05
      Pdh kW 2.20 2.60 2.60 3.20 3.20 5.20 6.20 6.60
      PERd % 92.0 98.8 98.8 96.4 96.4 79.2 81.6 82.0
    Bedingung B (2 °C TK/1 °C FK) Cdh (Absinken Heizen)   1.00 0.900 0.900 0.900 0.900 1.00 1.00 1.00
      COPd   3.75 3.26 3.26 3.69 3.69 3.25 3.20 3.19
      Pdh kW 1.40 2.00 2.00 2.40 2.40 3.20 3.80 4.00
      PERd % 150 130 130 148 148 130 128 128
    Bedingung C (7 °C TK/6 °C FK) Cdh (Verschlechterung Heizung)   0.900 0.900 0.900 0.900 0.900 0.900 0.900 0.900
      COPd   5.92 4.42 4.42 5.58 5.58 5.50 5.50 5.50
      Pdh kW 1.60 2.60 2.60 3.20 3.20 5.20 5.20 5.20
      PERd % 237 177 177 223 223 220 220 220
    Bedingung D (12 °C TK/11 °C FK) COPd   8.65 5.54 5.54 7.79 7.79 7.56 7.56 7.56
      Pdh kW 1.60 3.00 3.00 3.60 3.60 6.10 6.10 6.10
      PERd % 346 222 222 312 312 302 302 302
    Tol (Temperatur-Betriebsgrenze) COPd   0.890 1.05 1.05 0.980 0.980 1.22 1.13 1.08
      Pdh kW 0.800 1.00 1.00 1.20 1.20 5.70 6.40 6.80
      PERd % 35.6 42.0 42.0 39.2 39.2 48.8 45.2 43.2
      TOL °C -20.0 -20.0 -20.0 -20.0 -20.0 -20.0 -20.0 -20.0
      WTOL °C 55.0 55.0 55.0 55.0 55.0 55.0 55.0 55.0
    Bedingung G (-15 °C TK/–) COPd   1.25 1.42 1.42 1.33 1.33 1.51 1.50 1.42
      Pdh kW 2.90 3.60 3.60 4.30 4.30 7.10 8.40 8.90
      PERd % 50.0 56.8 56.8 53.2 53.2 60.4 60.0 56.8
    Tbiv (bivalente Temperatur) COPd   1.25 1.42 1.42 1.33 1.33 1.51 1.50 1.42
      Pdh kW 2.90 3.60 3.60 4.30 4.30 7.10 8.40 8.90
      PERd % 50.0 56.8 56.8 53.2 53.2 60.4 60.0 56.8
      Tbiv °C -15.0 -15.0 -15.0 -15.0 -15.0 -15.0 -15.0 -15.0
    Nenn-Heizleistung Zusatzheizung Psup (bei Tdesign -22°C) kW 3.50 4.40 4.40 5.20 5.20 8.70 10.3 11.0
  Warmes Klima Wasserauslass 55 °C Allgemein Jährlicher Energieverbrauch kWh 1,170 1,900 1,900 1,930 1,930 2,640 3,280 3,430
      Ƞs (Saisonale Effizienz Raumheizen) % 179 145 145 171 171 135 144 145
      Prated bei 2°C kW 4.00 5.00 5.00 7.00 7.00 8.00 10.0 10.0
    Bedingung B (2 °C TK/1 °C FK) Cdh (Absinken Heizen)   1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
      COPd   2.11 2.29 2.29 2.15 2.15 1.82 1.90 1.78
      Pdh kW 4.30 5.50 5.50 6.60 6.60 7.60 9.80 10.3
      PERd % 84.4 91.6 91.6 86.0 86.0 72.8 76.0 71.2
    Bedingung C (7 °C TK/6 °C FK) Cdh (Verschlechterung Heizung)   1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
      COPd   3.76 3.41 3.41 3.70 3.70 3.07 3.22 3.25
      Pdh kW 2.80 3.50 3.50 4.20 4.20 4.90 6.30 6.60
      PERd % 150 136 136 148 148 123 129 130
    Bedingung D (12 °C TK/11 °C FK) Cdh (Absinken Heizen)   0.900 0.900 0.900 0.900 0.900 0.900 0.900 0.900
      COPd   7.26 4.86 4.86 6.52 6.52 5.88 5.88 5.88
      Pdh kW 1.60 2.90 2.90 3.50 3.50 5.40 5.40 5.40
      PERd % 290 194 194 261 261 235 235 235
    Tbiv (bivalente Temperatur) COPd   2.11 2.29 2.29 2.15 2.15 1.82 1.90 1.78
      Pdh kW 4.30 5.50 5.50 6.60 6.60 7.60 9.80 10.3
      PERd % 84.4 91.6 91.6 86.0 86.0 72.8 76.0 71.2
      Tbiv °C 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00
  Wasserauslass 35°C für durchschnittliches Klima Allgemein SCOP   4.55 4.14 4.14 4.20 4.20 3.98 3.90 3.80
      Jährlicher Energieverbrauch kWh 2,050 2,460 2,460 3,490 3,490 5,380 7,250 8,270
      Ƞs (Saisonale Effizienz Raumheizen) % 179 163 163 165 165 156 153 149
      Prated bei -10 °C kW 4.50 4.96 4.96 7.10 7.10 11.2 14.5 16.0
      Jährlicher Energieverbrauch (GCV) Gj 7.36 8.87 8.87 12.6 12.6 19.4 26.1 29.8
      Saisonale Effizienzklasse Raumheizen   A+++ A++ A++ A++ A++ A++ A++ A+
    Bedingung A (-7 °C TK/-8 °C FK) COPd   3.02 2.64 2.64 2.64 2.64 2.63 2.63 2.33
      Pdh kW 4.03 4.40 4.40 6.29 6.29 8.88 10.7 12.4
      PERd %           105 105 93.2
    Bedingung B (2 °C TK/1 °C FK) Cdh (Verschlechterung Heizung)   0.985 0.986 0.986 0.986 0.986 1.00 1.00 1.00
      COPd   4.33 4.10 4.10 4.10 4.10 4.05 4.07 3.74
      Pdh kW 2.53 3.93 3.93 3.93 3.93 6.03 7.71 8.62
      PERd %           162 163 150
    Bedingung C (7 °C TK/6 °C FK) Cdh (Verschlechterung Heizung)   0.970 0.969 0.969 0.969 0.969 0.940 1.00 0.940
      COPd   6.06 5.70 5.70 5.70 5.70 6.77 5.71 6.77
      Pdh kW 1.80 2.52 2.52 2.52 2.52 5.74 5.05 5.74
      PERd %           271 228 271
    Bedingung D (12 °C TK/11 °C FK) Cdh (Absinken Heizen)   0.966 0.962 0.962 0.962 0.962 0.920 0.930 0.920
      COPd   8.52 7.13 7.13 7.13 7.13 8.97 6.71 8.97
      Pdh kW 2.21 2.58 2.58 2.58 2.58 6.50 5.16 6.50
      PERd %           359 268 359
    Tol (Temperaturbetriebsgrenze) COPd   2.69 2.34 2.34 2.34 2.34 2.34 2.60 2.05
      Pdh kW 4.50 4.43 4.43 6.49 6.49 8.76 12.6 11.7
      PERd %           93.6 104 82.0
      TOL °C -10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0
      WTOL °C 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0
    Tbiv (bivalente Temperatur) COPd   2.69 2.47 2.47 2.47 2.47 2.82 2.83 2.56
      Pdh kW 4.50 4.56 4.56 6.67 6.67 9.09 11.6 12.1
      PERd %           113 113 102
      Tbiv °C -10.0 -8.00 -8.00 -8.00 -8.00 -5.00 -5.00 -4.00
    Nennleistung Wärmeabgabe Zusatzheizer Psup (bei Tdesign -10 °C) kW   0.530 0.530 0.610 0.610 2.44 1.93 4.35
Hinweise (1) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: 7 °C TK/6 °C FK (1) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: 7 °C TK/6 °C FK (1) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: 7 °C TK/6 °C FK (1) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: 7 °C TK/6 °C FK (1) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: 7 °C TK/6 °C FK (1) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: 7 °C TK/6 °C FK (1) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: 7 °C TK/6 °C FK (1) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: 7 °C TK/6 °C FK
  (2) - EW 40 °C; AW 45 °C; Umgebungsbedingungen: 7 °C TK/6 °C FK (2) - EW 40 °C; AW 45 °C; Umgebungsbedingungen: 7 °C TK/6 °C FK (2) - EW 40 °C; AW 45 °C; Umgebungsbedingungen: 7 °C TK/6 °C FK (2) - EW 40 °C; AW 45 °C; Umgebungsbedingungen: 7 °C TK/6 °C FK (2) - EW 40 °C; AW 45 °C; Umgebungsbedingungen: 7 °C TK/6 °C FK (2) - EW 40 °C; AW 45 °C; Umgebungsbedingungen: 7 °C TK/6 °C FK (2) - EW 40 °C; AW 45 °C; Umgebungsbedingungen: 7 °C TK/6 °C FK (2) - EW 40 °C; AW 45 °C; Umgebungsbedingungen: 7 °C TK/6 °C FK
  (3) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: -7 °C TK/-8 °C FK (3) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: -7 °C TK/-8 °C FK (3) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: -7 °C TK/-8 °C FK (3) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: -7 °C TK/-8 °C FK (3) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: -7 °C TK/-8 °C FK (3) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: -7 °C TK/-8 °C FK (3) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: -7 °C TK/-8 °C FK (3) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: -7 °C TK/-8 °C FK
  (4) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: 2 °C TK/1 °C FK (4) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: 2 °C TK/1 °C FK (4) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: 2 °C TK/1 °C FK (4) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: 2 °C TK/1 °C FK (4) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: 2 °C TK/1 °C FK (4) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: 2 °C TK/1 °C FK (4) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: 2 °C TK/1 °C FK (4) - EW 30 °C; AW 35 °C; Umgebungsbedingungen: 2 °C TK/1 °C FK
  (5) - Bedingung 1: Kühlen: Ta 35°C - LWE 18°C (DT = 5°C); Heizen: Ta TK/FK 7°C/6°C - LWC 35°C (DT = 5°C) (5) - Bedingung 1: Kühlen: Ta 35°C - LWE 18°C (DT = 5°C); Heizen: Ta TK/FK 7°C/6°C - LWC 35°C (DT = 5°C) (5) - Bedingung 1: Kühlen: Ta 35°C - LWE 18°C (DT = 5°C); Heizen: Ta TK/FK 7°C/6°C - LWC 35°C (DT = 5°C) (5) - Bedingung 1: Kühlen: Ta 35°C - LWE 18°C (DT = 5°C); Heizen: Ta TK/FK 7°C/6°C - LWC 35°C (DT = 5°C) (5) - Bedingung 1: Kühlen: Ta 35°C - LWE 18°C (DT = 5°C); Heizen: Ta TK/FK 7°C/6°C - LWC 35°C (DT = 5°C) (5) - Bedingung 1: Kühlen: Ta 35°C - LWE 18°C (DT = 5°C); Heizen: Ta TK/FK 7°C/6°C - LWC 35°C (DT = 5°C) (5) - Bedingung 1: Kühlen: Ta 35°C - LWE 18°C (DT = 5°C); Heizen: Ta TK/FK 7°C/6°C - LWC 35°C (DT = 5°C) (5) - Bedingung 1: Kühlen: Ta 35°C - LWE 18°C (DT = 5°C); Heizen: Ta TK/FK 7°C/6°C - LWC 35°C (DT = 5°C)
  (6) - Bedingung 2: Kühlen: Ta 35°C - LWE 7℃ (DT = 5°C); Heizen: Ta TK/FK 7°C/6°C - LWC 45℃ (DT = 5°C) (6) - Bedingung 2: Kühlen: Ta 35°C - LWE 7℃ (DT = 5°C); Heizen: Ta TK/FK 7°C/6°C - LWC 45℃ (DT = 5°C) (6) - Bedingung 2: Kühlen: Ta 35°C - LWE 7℃ (DT = 5°C); Heizen: Ta TK/FK 7°C/6°C - LWC 45℃ (DT = 5°C) (6) - Bedingung 2: Kühlen: Ta 35°C - LWE 7℃ (DT = 5°C); Heizen: Ta TK/FK 7°C/6°C - LWC 45℃ (DT = 5°C) (6) - Bedingung 2: Kühlen: Ta 35°C - LWE 7℃ (DT = 5°C); Heizen: Ta TK/FK 7°C/6°C - LWC 45℃ (DT = 5°C) (6) - Bedingung 2: Kühlen: Ta 35°C - LWE 7℃ (DT = 5°C); Heizen: Ta TK/FK 7°C/6°C - LWC 45℃ (DT = 5°C) (6) - Bedingung 2: Kühlen: Ta 35°C - LWE 7℃ (DT = 5°C); Heizen: Ta TK/FK 7°C/6°C - LWC 45℃ (DT = 5°C) (6) - Bedingung 2: Kühlen: Ta 35°C - LWE 7℃ (DT = 5°C); Heizen: Ta TK/FK 7°C/6°C - LWC 45℃ (DT = 5°C)
  (7) - Tamb 35 °C – LWE 18 °C (DT = 5 °C) (7) - Tamb 35 °C – LWE 18 °C (DT = 5 °C) (7) - Tamb 35 °C – LWE 18 °C (DT = 5 °C) (7) - Tamb 35 °C – LWE 18 °C (DT = 5 °C) (7) - Tamb 35 °C – LWE 18 °C (DT = 5 °C) (7) - Tamb 35 °C – LWE 18 °C (DT = 5 °C) (7) - Tamb 35 °C – LWE 18 °C (DT = 5 °C) (7) - Tamb 35 °C – LWE 18 °C (DT = 5 °C)
  (8) - T Umgebung 35°C – LWE 7°C (DT=5°C) (8) - T Umgebung 35°C – LWE 7°C (DT=5°C) (8) - T Umgebung 35°C – LWE 7°C (DT=5°C) (8) - T Umgebung 35°C – LWE 7°C (DT=5°C) (8) - T Umgebung 35°C – LWE 7°C (DT=5°C) (8) - T Umgebung 35°C – LWE 7°C (DT=5°C) (8) - T Umgebung 35°C – LWE 7°C (DT=5°C) (8) - T Umgebung 35°C – LWE 7°C (DT=5°C)
  (9) - TK/FK 7°C/6°C-LWC 35°C(DT=5°C) (9) - TK/FK 7°C/6°C-LWC 35°C(DT=5°C) (9) - TK/FK 7°C/6°C-LWC 35°C(DT=5°C) (9) - TK/FK 7°C/6°C-LWC 35°C(DT=5°C) (9) - TK/FK 7°C/6°C-LWC 35°C(DT=5°C) (9) - TK/FK 7°C/6°C-LWC 35°C(DT=5°C) (9) - TK/FK 7°C/6°C-LWC 35°C(DT=5°C) (9) - TK/FK 7°C/6°C-LWC 35°C(DT=5°C)
  (10) - TK/FK 7°C/6°C - LWC 45°C(Dt=5°C) (10) - TK/FK 7°C/6°C - LWC 45°C(Dt=5°C) (10) - TK/FK 7°C/6°C - LWC 45°C(Dt=5°C) (10) - TK/FK 7°C/6°C - LWC 45°C(Dt=5°C) (10) - TK/FK 7°C/6°C - LWC 45°C(Dt=5°C) (10) - TK/FK 7°C/6°C - LWC 45°C(Dt=5°C) (10) - TK/FK 7°C/6°C - LWC 45°C(Dt=5°C) (10) - TK/FK 7°C/6°C - LWC 45°C(Dt=5°C)